In this paper, the results of load-bearing fire test are introduced that targets a composite flooring system composed of a flat RC slab and an unprotected beam. When the unprotected steel beam applied as a secondary beam is exposed to fire, it loses strength at an early stage of fire. On the other hand, for flat RC slabs supported in 2 ways, when deflection increases, membrane stress occurs within the cross section of the slab, and as a result the load bearing capacity of the slab is improved due to this membrane action. In RC slabs in which two-tier reinforcements are arranged, when subjected to fire heating, the temperature at the upper-side reinforcement becomes lower than that at the lower-side reinforcement, and thus the tensile strength at the upper-side reinforcement is kept to a high level for a long time. As a result, it is forecast that the retention of strength by the slab due to the membrane action during fire will become more conspicuous. In order to understand these behaviors, a load-bearing fire test was carried out by means of standard fire heating in accordance with ISO 834, targeting a composite flooring system composed of a two-tier reinforcement-arranged flat RC slab and an unprotected steel beam. The following will summarize the results of the tests.