This paper provides theoretical calculations that predict the dielectric breakdown properties of carbon dioxide (CO 2 ) and its mixtures with 50% O 2 and 50% H 2 for a gas temperature range of 300–3500 K at 0.1 MPa. CO 2 is one of the most likely candidates for an environment-friendly arc-quenching medium to replace SF 6 in high-voltage circuit breakers. Initially, the electron energy distribution function (EEDF) is derived by solving the Boltzmann equation under the zero-dimensional two-term spherical harmonic approximation. Then the reduced ionization and attachment coefficients are obtained, based on the calculated EEDF. Finally, the critical reduced electric field strength ( E / N ) cr , which is defined as the value for which total ionization reactions are equal to total attachment reactions, is obtained and analysed. The results demonstrate the superior breakdown properties of a 50% CO 2 –50% O 2 mixture to those of both pure CO 2 and 50% CO 2 –50% H 2 . Nearly no deviation in ( E / N ) cr is found in a 50% CO 2 –50% O 2 mixture for gas temperatures up to 2500 K, and although there is clear reduction as the gas temperature is increased further to 3500 K, the value remains higher than that of pure CO 2 .
No takes yet. Share an insight, caveat, or question.
Zhao et al. (2014) studied this question.