Experimental and simulation study reveals two-phase condensation flow dynamics of R410A in a split refrigeration condenser, indicating reliable methods to evaluate alternative refrigerants.
This study examines how R410A condenses inside the condenser of a 1.5‑ton split vapor compression refrigeration unit operating under summer conditions. The unit was tested at an ambient temperature of 37.4 °C, with R410A entering the condenser at 77.6 °C, 28.5 bar (gauge), and 0.0035 kg/s, while the saturation temperature was 45.8 °C and the representative flow‑path length was 9.41 m through a 4 mm inner‑diameter copper tube. To interpret the flow behavior, a transient three‑dimensional CFD model was developed in ANSYS Fluent using the VOF method, the Lee phase‑change model, and surface‑tension effects. The results showed that the refrigerant entered as superheated vapor and gradually changed into annular and wavy‑annular flow as condensation progressed along the tube. The predicted vapor fraction decreased from nearly 1 at the inlet region to about 0.61 near the outlet, indicating strong condensate buildup downstream. The numerical results agreed well with the measured temperature trend and the observed flow images. Overall, the model captured the main thermal and flow features of R410A condensation and provides a useful basis for evaluating alternative refrigerants in the same condenser geometry.