Answers are grounded in this paper and cite their sources.
SF6is widely used in C-GIS as an insulating medium. However, SF6and its decomposition products can pollute environment and harm human health and equipment. Firstly, this paper verifies the high-energy discharge promotes CF3I to produce C2F6 and I2 by simulation. Therefore the paper puts forward the significance of using mixture gas to reduce the use of CF3I and control the produce of I2. Secondly, the partial discharge inception voltages in the positive half cycle of power frequency (PDIV+) of CF3I/CO2under different pressures, mixing ratios (k) and interelectrode distances were measured and compared with SF6/CO2. The results show that: when k is more than 10%, the PDIV+ of CF3I/CO2is close to or higher than SF6/CO2in the same experimental conditions; The PDIV+ of CF3I/CO2(30%-40%) at 0.15-0.2MPa can reach the level of pure SF6in 0.1MPa. The breakdown experiments under different electric fields shows that the breakdown characteristic of CF3I/CO2(30%-40%) at 0.15-0.2MPa can exceed the level of pure SF6at 0.1MPa. Considering the boiling point, producing of I2and insulating property, CF3I/CO2(30%-40%) is likely to replace SF6used in C-GIS.
No takes yet. Share an insight, caveat, or question.
Zhang et al. (2015) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: