We have developed a loss estimation method that is applicable to three-phase ac reactors using amorphous cores in a 400-kVA UPS. The method is based on measured the B–H curves and iron losses of the cores, modeled with magnetic simulations of a finite-element method considering the directions of the amorphous ribbon planes. The reactors are formed from wound cores. Two types of magnetic legs are proposed: structure A, toroidal-shaped with slits, and structure B, sector prism-shaped cut from a wound core. Their unit volumes are shrunk by 9% and 19%, respectively, compared with that of a conventional silicon-steel core reactor. Both reactors have about half the total losses of the conventional silicon-steel core reactor, resulting in increased UPS efficiencies of up to 0.55%. The calculated iron losses at the pulse width modulation (PWM) carrier frequencies agree with measured losses within 10%. The accuracy of the loss estimation method for PWM-induced reactors is discussed. The method is confirmed to enable accurate design of a reactor for filtering in a high-efficiency inverter system.
No takes yet. Share an insight, caveat, or question.
Kurita et al. (2013) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: