Answers are grounded in this paper and cite their sources.
This paper presents a new partial discharge (PD) location technique for power cables. Unlike commonly used time-domain reflectometry (TDR) methods, this technique is based on the analysis of phase difference between the direct and reflected waves of a PD pulse measured at the cable end. The phase difference at various frequencies can be obtained from the cross Fourier spectral density function. After implementing a phase unwrapping algorithm, the defect is located. This technique has been tested using the Electromagnetic Transient Program (EMTP) on the model of a 20 kV, 1-km underground cable. The simulation takes into account the frequency-dependent parameters of the cable and the measurement accuracy of the A/D converter (8-bit). The signal-to-noise ratio (SNR) varies from 10 dB to -5 dB for all computer simulations. The statistical results are given to demonstrate the performance of the proposed technique.
No takes yet. Share an insight, caveat, or question.
Mardiana et al. (2010) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: