Answers are grounded in this paper and cite their sources.
Model structures representative of power transformer conductors and metallic components have been tested at elevated hot-spot temperatures to simulate operation at overloads. Three different types of cellulosic insulation in contact with hot-spots evolved visible gas bubbles at temperatures as low as 140°C, while hot metal in contact with oil alone produced no visible gas bubbles up to approximately 350°C. The dielectric strength of insulated conductors was observed to deteriorate moderately at temperatures in the 100°C to 150 °C range, but more rapidly at temperatures above 150°C. The experimental results have been analyzed and are discussed with relation to their potential significance to transformer loading practices.
No takes yet. Share an insight, caveat, or question.
McNutt et al. (1980) studied this question.