Answers are grounded in this paper and cite their sources.
Experimental validation demonstrates high efficiency and low harmonic distortion in an active compensation interface, highlighting its utility for smart-grid battery storage.
This paper presents the design, simulation, and experimental validation of an Active Compensation System (ACS) intended for bidirectional energy exchange between the utility grid and a battery energy storage system. The proposed architecture combines a bridgeless totem-pole power factor correction converter BLTP-PFC and a bidirectional CLLLC resonant DC/DC converter. A comparative evaluation of different converter topologies is performed considering efficiency, bidirectional operation capability, implementation complexity, and suitability for active compensation applications. Simulation and laboratory measurements verify operation in both charging and discharging modes. Experimental results demonstrate a maximum output power of 2.18 kW, power factor close to unity, current THD of 1.43%, and system efficiency exceeding 96%. The results confirm the suitability of the proposed topology for future smart-grid, renewable-energy, and battery-energy-storage applications.
No takes yet. Share an insight, caveat, or question.
Praženica et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: