Answers are grounded in this paper and cite their sources.
With the development of convenience stores based on their convenience, considering energy-saving designs for convenience stores is crucial for national energy-saving policies. In this article, in addition to energy-saving, the customer experience in convenience stores is also discussed. PHOENICS is used for numerical simulations in the current research report. This article uses the basic k-ε turbulent model in CFD to simulate temperature and energy variations in convenience stores (commercial buildings). Considering the phenomenon of flow mixing within the air curtain zone, it is essential to include a buffer around the boundary, which is subsequently proposed in the CFD simulation. The temperature setting is based on Taiwan climate temperature. Through temperature and velocity analysis, the study discusses considerations for customer experience. The results from CFD show that a well-designed air curtain at the entrance of a convenience store can reduce energy loss, making it an effective energy-saving tool. In addition, setting the air curtain temperature to 25 °C has been found to significantly contribute to energy savings. The simulation results provide better settings for convenience store air conditioning operations. By analyzing the problem and identifying possible optimal solutions, the use of CFD can effectively improve convenience store energy costs.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: