This is the authors' abstract. We don't add key points for this paper.
Future multi-terminal dc networks are envisioned for the large-scale integration of renewable energy sources into today's power systems. An essential aspect for the reliable operation of these systems is the fast and selective dc-side fault handling and separation of faulted lines. The objective of this paper is the development and evaluation of a multi-terminal dc protection strategy based on fault-blocking converters (e.g., full-bridge based modular multi-level converters) and high-speed switches. Both a suitable fault control and a new high-speed switch design for a fast separation of faulted dc lines are elaborated. The novel concept is intended to reduce the requirements on the high-speed switches compared to dc circuit breakers and to ensure a fast restoration of the active power transmission capability, as well as the dc voltage. The fault-clearing strategy is analyzed using electromagnetic transient (EMT) simulations under variation of the fault location, type, and resistance. The investigations are carried out in a cable-based multi-terminal HVdc system with full-bridge modular multi-level converters in symmetrical monopole configuration.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Ruffing et al. (2018) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: