Answers are grounded in this paper and cite their sources.
An investigation has been carried out of cathode spot dynamics in a triggered vacuum arc in a demountable chamber. A rectangular current pulse of 1-5 kA, 1-5 ms has been used. Sufficient statistics were collected. The expansion of a cathode spot ring on a clean, pure metal surface was corroborated to be a retrograde movement in the self-magnetic field which obeys the same law as the movement of a single spot in an external magnetic field. The influence of a contact gap of 0.5-8 mm and current on the dynamics of cathode spots was investigated. The gap dependence of the proportional coefficient between the spot velocity and magnetic field in the case of a pure copper cathode was obtained. A phenomenon was discovered, where a group of cathode spots form in the short arcs on the CuCr cathodes after a transition diffuse arc stage. The follow-up investigation revealed that a close interrelation exists between the cathode and anode processes in short arcs. This interrelation is responsible for the appearance of the discovered phenomenon. Short-circuit performance tests conducted for a commercial vacuum interrupter proved cathode spot group formation to be responsible for the interruption failure at short contact gaps.
No takes yet. Share an insight, caveat, or question.
Chaly et al. (1997) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: