Answers are grounded in this paper and cite their sources.
Benchmark evaluation reveals substantial performance drops for physics-informed detectors on real-world industrial control data, highlighting critical failures in hybrid decision pathways.
Physics-informed anomaly detection for industrial control systems (ICSs) is usually validated on synthetic data. How much of that performance survives on real hardware-in-the-loop (HIL) data is an open question. We re-implement PhySec-Edge, a hybrid BiLSTM/β-VAE/GAT/Kalman pipeline, as a full architecture and evaluate it on HAI 23.05. The gap is consistent across five seeds. AI-only F1 falls from 0.774 (synthetic) to 0.525 (HAI); the full hybrid falls from 0.798 to 0.512. The components diverge. PVE residual sharing transfers but weakens on real data (ΔF1 = +0.010 ± 0.008 across five seeds against +0.017 synthetic; ΔMCC = +0.013, positive in every seed). The PVE NIS decision score fails outright (raw FPR = 0.482; a correction brings it to 0.013, but detection does not recover). Under the retrospective fixed-FPR comparison, the preferred configuration is GNN+BiLSTM (F1 = 0.530 ± 0.002), outperforming full-EADE fusion (0.512 ± 0.003). From this split we derive the information-vs-decision pathway distinction, a way to reason about component-level generalization in hybrid architectures. We then set out what it means for physics-informed ICS detector design and edge deployment.
No takes yet. Share an insight, caveat, or question.
Radovanović et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: