Answers are grounded in this paper and cite their sources.
Three‐phase load asymmetry causes a useless current loading of the supply source and this loading increases even more if the supply voltage is non‐sinusoidal. This loading can be expressed quantitatively with the unbalanced current iuof RMS value ||iu||. A whole compensation of the unbalanced current iuwas proved to be possible with reactive balancing circuits, however, it may be very complex. This paper shows that a substantial minimization of the unbalanced current iumay be achieved with such a circuit, but of much lower complexity. The method suggested requires that the unbalanced admittances Anof the load for harmonic frequencies are known. A harmonic analysis that provides the complex RMS values of the phase voltages and currents harmonics in a cross‐section between the load and the source enables us to determine these admittances and design the balancing circuit. It was shown, moreover, that the reduction of the unbalanced current iucan be integrated with the reactive current irminimization.
No takes yet. Share an insight, caveat, or question.
Leszek S. Czarnecki (1993) studied this question.