This is the authors' abstract. We don't add key points for this paper.
SUMMARY Online partial discharge (PD) measurement is very important for insulation monitoring of high‐voltage equipment. One of the biggest challenges performing online monitoring is discrimination between PD detect signals and external noises. Experimental results using high‐frequency current transformer (CT) sensor show that the current waveforms associated with various PD signals are all damped cosine waveforms, and have unique frequency and decay times of damped oscillation. Therefore, we focused attention on the damped oscillation waveform of the PD current, especially damped cosine waveform having a different number of oscillations. In addition to this, the noise discrimination method using wavelet transform or short‐time Fourier transform is effective. Those noise discriminating processes are applicable to online PD current measurement system.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Torii et al. (2018) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: