Air samples taken in a hospital undergoing construction and analyzed with a quantitative polymerase chain reaction (qPCR) assay for the Aspergillus genus did not show elevated concentrations of Aspergillus or particulate matter with a diameter of 5 microm or less in patient areas. Air samples from the construction zone indicated the containment system, which used polyethylene film barrier and negative pressure, was effective.