We present a novel microsystem methodology to detect voltage and current disturbances in high power distribution lines. Our system employs a custom designed piezoelectric transformer operating at 50/60 Hz, as an alternative to the bulky electromagnetic transformer, to detect disturbances up to few kilohertz. In the frequency range of 10 Hz to 250 Hz, the piezotransformer steps down the 10-150 V input voltage with a linearity of ±1%. This stepped down piezo output is treated with a signal processing system designed based on frequency composition of the piezo signal, to generate a digital output. A 7-bit digital output from this system reports various types of line disturbances within 3 ms of occurrence. We present details of the proposed system, supported both by numerical simulations and experimental results.
No takes yet. Share an insight, caveat, or question.
Lele et al. (2014) studied this question.
Synapse has enriched one closely related paper. Consider it for comparative context: