In this study, a modified version of IEEE 34-bus test feeder with two fixed speed wind generators is considered. In the proposed method, at first, the type of short circuit is determined using the 3-phase current data that are measured at the substation. Then, to train and test the Artificial Neural Network (ANN), different operating patterns are produced for each type of short circuit. In order to cover the total operating space of the radial distribution network by ANNs; fault location, fault resistance, load of every node and power of distributed generations DGs are changed in each pattern. For each type of short circuit, three different ANNs are used for estimation of the distance of fault to the substation and the interconnection of DGs. Inputs of the ANNs are 3-phase voltage and current which measured at the substation and the DG buses in pre fault and post fault stages. The results show low estimation error in testing of ANNs. For exact fault location, the estimated fault distance to the substation is compared with the estimated fault distance to the DG buses. Finally, the sensitivity of ANNs to the measuring error of the input data is examined.