Answers are grounded in this paper and cite their sources.
To achieve carbon neutrality by 2050, electric vehicles (EVs) are promoted and EV fast chargers are expected to become part of the public infrastructure. To feed power to EV fast chargers installed in highway rest areas, the authors have proposed a 33-kV dedicated cable supply system installed along the highway. Due to the large capacitance of a cable system, harmonics may be of concerns for the operation of the proposed system. Therefore, this paper presents a study of harmonics occurring in the 33-kV dedicated cable supply system to feed EV fast chargers. First, the cause of the harmonics is identified by deriving resonance frequencies of the equivalent circuit of the cable supply system. Then, the harmonic resonance phenomenon is verified by electromagnetic transient (EMT) simulations. The results indicate conditions with which harmonic resonance may occur in the cable supply system. To perform the simulations, the EMT simulation models of distribution substations and EV fast chargers are picked up from the generic EMT simulation models prepared in XTAP (eXpandable Transient Analysis Program) for distribution and microgrid simulations. It should be noted that the harmonics simulations mentioned above can readily be performed by picking up necessary models from the model library.
No takes yet. Share an insight, caveat, or question.
Shoji et al. (2023) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: