Condensers and evaporators in refrigeration systems are composed of several straight tubes connected by U-bends. U-bends create higher flow resistance than straight tubes due to flow disruptions, which could extend to adjoining straight tubes. This study presents new data for two-phase flow pressure drop in U-bends and contiguous straight tubes with ammonia. The study is performed at saturation temperature of 10 and −15 °C, with mass flux between 10 and 50 kg/m2s and vapor quality between 0.1 and 0.9. The tube nominal outer diameter was 15.9 mm with 1.6 mm wall thickness. The bend radius to tube diameter ratio was 2.5, and the bend was oriented horizontally. Up to 1.6 times higher pressure drop in the U-bend is observed as compared to straight tube sections subjected to changes in flow conditions. Pressure drop increases with mass flux and vapor quality and decreases with saturation temperature. The pressure drop increase is more significant with an increase in mass flux between 10 and 30 kg/m2s. Additionally, a substantial disruption in pressure gradients near the U-bend, both upstream and downstream, was observed. Comparative analysis revealed that only a few correlations predicted the present data at limited conditions for the straight tube and bend.