Coastal low-voltage isolated or impedance-earthed-neutral (IT) systems are capable of continuous power supply following the first earth fault. However, environmental erosion and converter-related system unbalance render the neutral-to-earth characteristics of such systems highly dependent on insulation performance and protective-earthing-path conditions. This paper proposes an environmental-state-driven and traceable configuration method for fixed series resistance–inductance neutral-to-earth branches. The method represents environment-dependent variations in system insulation and protective-earthing paths through temperature, humidity, salt contamination, and component aging and establishes four coupled environmental states accordingly. For each candidate neutral branch configuration, three critical indicators, i.e., neutral-point displacement voltage, first-earth-fault current, and touch voltage, are comprehensively evaluated. A common robust feasible region satisfying all prescribed environmental states is extracted through full-state constraint screening. Infeasible configuration candidates are traced to their dominant environmental states and restrictive constraints. Furthermore, a Pareto max–min selection criterion is adopted to determine the optimal configuration, which maximizes the minimum normalized safety margin without requiring additional empirical trade-off weights or online parameter retuning. A 400 V primary case study, complemented by cross-site climatic and electrical-system transferability assessments, demonstrates the applicability of the proposed framework over the investigated conditions.
No takes yet. Share an insight, caveat, or question.
Li et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: