Answers are grounded in this paper and cite their sources.
Mechanical winding damages in transformers are quite common. Inherently these damages at an advanced stage are very complex in appearance and are a challenge to represent accurately or model by any known means. Alternatively, as a first approximation, one might treat an incipient damage as a combination of one or more localized and discrete radial displacements and/or axial displacements. When 3-Φtransformers suffer a minor and discrete radial displacement, the measured FRA magnitude reveals minor deviations (compared to reference-case). However, it is impossible to infer the nature of damage and which phase has actually suffered the damage. For diagnostics, it is crucial to detect such instances at the earliest. This paper describes a simple method based on measured FRA and winding shunt capacitance$-$leading to identification of phase undergoing radial displacement. The method is based on authors' recent analytical expressions, which connects winding's inductances and capacitances to open-circuit and short-circuit natural frequencies. Mathematical formulation to identify which phase contains radial displacement for both Y- andΔ- winding is presented first, followed by experiments on a 3.5 MVA, 33 kV setup. The method is extended to identify a simultaneous and discrete radial+axial displacement, occurring in one phase of a 3-Φwinding.
No takes yet. Share an insight, caveat, or question.
Biswas et al. (2023) studied this question.