Answers are grounded in this paper and cite their sources.
The gas-puffer effect has important effects on the interruption capability of a molded case circuit breaker (MCCB). In this paper, on the basis of a simplified model of an arc chamber with a single break, the effect of back-volume of an arc-quenching chamber on arc behavior in an MCCB is investigated. Firstly, using a 2-D optical-fiber arc-motion measurement system, experiments are performed to study the effect of back-volume on the arc-motion and gas pressure in an arc-quenching chamber. We demonstrate that the lower back-volume of the arc-quenching chamber is, the higher the pressure and the better the arc motion will be. Then, corresponding to the above experiments, the gas pressure inside the arc-quenching chamber is calculated using the integral conservation equation. The simulation results are consistent with the experimental results.
No takes yet. Share an insight, caveat, or question.
Dai et al. (2008) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: