Answers are grounded in this paper and cite their sources.
Purpose: High-voltage electrical equipment requires a grounding installation in order to protect lives in freshwater swamps with a hydrogen potential of 6.75. To build a grounding structure, it is required to know the resistance value and grounding materials, namely copper-coated rod electrodes at different depths. Research methodology: The research was conducted in a freshwater swamp close to the shampooing substation using field observations and direct measurement of soil resistance values, followed by a literature review and comparisons using COMSOL simulation and FEM Analysis. Results: The results of direct research and simulations indicate that in order to accomplish a grounding resistance value < 5 ohms according to the PUIL 2011 standard for a single rod system made of copper, it is necessary to optimize the depth of the grounding electrode within a range of 10 meters, which differs from the simulation results of ground resistance measurement and the Comsol application. The percentage error is 1.05%. Limitations: This research analyzes the results of measurements and grounding analysis using Comsol Multiphysics at a depth of 1 meter for a particular type of copper-coated round rod electrode at depths of 1, 1.5, and 2 meters. Contributions: The results of the study offer information on the usefulness of grounding resistance in freshwater wetlands with a pH greater than 6, where several rod electrode types are utilized to compare future research.
No takes yet. Share an insight, caveat, or question.
Putra et al. (2023) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: