One of the requirements for a safe soil construction installation is a low soil resistance value in accordance with standards, including those applicable in Indonesia, namely PUIL 2000 and PUIL 2011 with a value of 0 Ω to 5 Ω, including the value of soil resistance in grounding arrester at LA distribution substations 0031.Because the objective of the arrester is to drain the lightning surge voltage in order to safeguard the distribution substation, it must have a good and standard grounding system, ideally with a resistance below 5.With the initial measurement of the grounding system having a value of 11.5 Ω, a study is required to reduce the value of the soil resistance, from a series of analytical calculations and soil types, so that a decrease in soil resistance is obtained which is considered the PUIL standard, namely 3.4 at arrester ground resistance.The smaller the resistance value obtained, the smaller the Ground Potential Rise (GPR) effect at the Distribution Substation.