Answers are grounded in this paper and cite their sources.
In this paper, we present an adaptive observer-based, closed-loop feedback method to estimate three-phase grid voltage parameters, including frequencies, amplitudes, and phase angles under grid unbalanced faults and harmonic voltage disturbances. We treat the three-phase grid voltage signal as a solution of a parameterized dynamic system involving the unknown parameters-the fundamental and harmonic frequencies. Based on the parameterized dynamic model thus obtained, an adaptive observer is then proposed for achieving asymptotic estimation of the three-phase grid voltage parameters, that is, estimations of frequencies, amplitudes, and phase angles with zero steady-state error. This conclusion is proved rigorously by means of the Lyapunov stability theory, passivity, and La Salle's invariance principle. Both numerical simulations via MATLAB and dSPACE-based experiments are conducted to demonstrate the effectiveness and performance of the proposed estimation scheme.
No takes yet. Share an insight, caveat, or question.
Dai et al. (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: