Answers are grounded in this paper and cite their sources.
The behaviour of a power transformer is complex and difficult to predict during transient conditions or during operation at frequencies below or above its nominal frequency, a phenomenon common in renewable energy plants due to harmonic distortion. Furthermore, the accuracy of a power system simulation depends on the models of critical subsystems such as the power transformers. This paper presents the use of a unique excitation waveform comprising of pseudo-random current impulses to accurately identify the wideband characteristics of a power transformer. By injecting the excitation waveform to the relevant transformer terminals, frequency responses are determined by cross-correlation of the perturbation signal, and the measured response. Compared to the traditional transformer identification methods, the pseudo-random current impulses offer a wideband excitation with a higher degree of controllability such that its spectral energy can be focused in the frequency band of interest. The proposed method was investigated on a 16 kVA, 22 kV/240 V single-phase transformer. The obtained wideband frequency responses provide useful information in harmonic penetration and over-voltage studies and are also used to estimate, with a high degree of accuracy, the lumped parameters of the equivalent transformer broadband circuit model.
No takes yet. Share an insight, caveat, or question.
Mwaniki et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: