Answers are grounded in this paper and cite their sources.
This study involves the development of an air-cooled condenser with porous lattice P-cell structures of 7 mm unit cell size on the air-side from an aluminium alloy (AlSi10Mg) powder by selective laser melting (SLM). The internal flow channels for enhanced condensation of R134a were designed with triangular cross-sections and a hydraulic diameter of 5 mm. Experiments were conducted to evaluate the condenser's thermohydraulic performance. The results demonstrate that the P-cell design increased the heat transfer rate per unit volume and per air mass flow rate of the air-cooled condenser by a factor of 2.81 as compared to a conventional plate fin-and-tube heat exchanger. The fan power efficiency is comparable to a conventional plate-fin-and-tube heat exchanger. The feasibility of using SLM to fabricate a robust air-cooled condenser for high pressure operation is demonstrated.
No takes yet. Share an insight, caveat, or question.
Samad et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: