Answers are grounded in this paper and cite their sources.
This study investigates the performance of an ethylene glycol/water (EG/Water) fluid at a 40:60 volume ratio, a commonly used base fluid in heating and cooling systems. The evaluation focuses on analyzing heat transfer coefficients and pressure drops. The research adopts an experimental approach, utilizing a test section made of pure copper with an inner diameter of 16 mm, an outer diameter of 19 mm, and a length of 1500 mm. The volume ratio of EG/Water at 40:60 is an input parameter, along with varying fluid flow rates controlled by a valve, ranging from 2 to 18 liters per minute. Two tubular heaters with a combined capacity of 2000 W are attached to the copper pipe, regulated by a 3000 W voltage regulator. Electric current is measured with ammeters. The experimental results reveal that the heat transfer coefficient of the EG/Water fluid increases as the fluid flow rate rises. The highest heat transfer coefficient is achieved at 18 L/min, while the lowest is observed at 4 L/min. Pressure drop increases with higher flow rates, but this does not significantly affect the friction factor, as it undergoes a noticeable decrease while the Reynolds number increases.
No takes yet. Share an insight, caveat, or question.
Junaedi et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: