This is the authors' abstract. We don't add key points for this paper.
This presents a reactive power control strategy for the single delta bridge cell modular multilevel cascaded converter (SDBC-MMCC) for static synchronous compensator (STATCOM) under asymmetric voltage conditions. An average power balancing method is proposed to support continuous injection of reactive power under grid voltage fault conditions, considering sub-module capacitor voltage balancing and STATCOM maximum phase current protection. Analytical solutions of the STATCOM phase currents are presented. A maximum current limit control scheme is proposed to ensure continuous reactive power injection and STATCOM operation under unbalanced voltage condition. The fault-ride through capability of the SDBC STATCOM under asymmetrical condition is analyzed using the proposed method. A comparative analysis shows that the current requirement of the proposed strategy is superior to the zero-sequence current balancing technique.
No takes yet. Share an insight, caveat, or question.
Oghorada et al. (2020) studied this question.