Answers are grounded in this paper and cite their sources.
This paper investigates the damping degradation of power system low-frequency electromechanical oscillations caused by the open-loop modal resonance. The investigation is based on a closed-loop interconnected model of a multimachine power system, wherein, the electromechanical dynamics of a synchronous generator being examined and the remainder of power system are modeled as two separate open-loop subsystems. The open-loop modal resonance is the closeness of an open-loop electromechanical oscillation mode of the synchronous generator to an open-loop electromechanical oscillation mode of the power system on the complex plane. Theoretical analysis indicates that when the open-loop modal resonance happens, the dynamic interactions between the synchronous generator and the remainder of power system are strong and degrade the damping of the low-frequency electromechanical oscillations. Test results in two example power systems show that the synchronous generator geographically far away took part in the local low-frequency electromechanical oscillations when the open-loop modal resonance occurred. The macroscopic effect of the open-loop modal resonance was the expansion of area on the complex plane, where the electromechanical oscillation modes were located, when the scale of the power systems increased.
No takes yet. Share an insight, caveat, or question.
Du et al. (2018) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: