Answers are grounded in this paper and cite their sources.
The electric field distortion caused by the high voltage current environment in the cable terminal will greatly increase the failure probability and reduce the operation safety; therefore, it is necessary to ensure the uniform distribution of the electric field in the terminal. This paper briefly introduced the high-voltage cable terminal and non-linear materials. The traditional silicone rubber and the silicone rubber added with nano-SiO 2 were prepared. The electrical conductivity of the two silicone rubbers was tested, and the electric field of the cable terminal was simulated. The results demonstrated that the nano-SiO 2 improved silicone rubber had a higher non-linear conductivity and was less affected by temperature. The calculation results of the simulation model also showed that the distribution of the internal field strength was more uniform, and the maximum field strength on the reinforced insulation was smaller after the improved silicone rubber was used as the reinforced insulation.
No takes yet. Share an insight, caveat, or question.
Li et al. (2021) studied this question.