Answers are grounded in this paper and cite their sources.
To solve the problem of the location of the fault point of single-pole-to-ground faults in the transmission lines of MMC-HVDC systems, this paper designs a fault location system based on support vector machine (SVM). The waveform of the traveling wave after the fault occurs is collected as a feature, and the regression mechanism of the SVM is utilized to achieve fault location. Because it is very difficult to locate high-resistance ground faults, this paper first analyzes the waveform characteristics of high-resistance ground faults. Next, three steps are proposed to reduce the influence of grounding resistance on fault location. These steps include using the active pulse waveform as a new feature, classifying the samples according to ground resistance values before training regression models, and a method for adaptively extracting fault distance features is proposed. Finally, a complete location system design is proposed, and its workflow is illustrated. After the simulation test, the proposed location system only needs to obtain a single-ended fault voltage waveform at a fault recording frequency of 20 kHz to achieve an accurate location of single-pole-to-ground faults for different values of grounding resistance.
No takes yet. Share an insight, caveat, or question.
Wu et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: