Answers are grounded in this paper and cite their sources.
SYNOPSIS In this paper the results of a CFD investigation for a push-pull local ventilation system are presented. The velocity field and the capture efficiency prediction are investigated for different system arrangements. The analysis is carried out for systems respectively with and without fluid-dynamic obstacle in the working plane and for dust pollutants with particle diameters ranging from 1.0 to 100 μm and emission velocities between 1.0 and 7.0 m/s. The analysis, carried out using the commercial code FLUENT, shows that the system performances are dependent on operating conditions and are influenced by the presence of the above-mentioned obstacle on the working plane. In the case of working plane emission without obstacle the system capture efficiency is in general very low never exceeding 25%. Higher efficiencies are instead achieved for particle emission from a vessel placed in the system's working plane centre. In this case even unitary peak efficiencies are reached for particular operating conditions.
No takes yet. Share an insight, caveat, or question.
Betta et al. (2007) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: