This paper describes how direct evaporative coolers can be used to improve the energy efficiency of air-cooled chillers in various operating conditions and with different strategies for staging condenser fans. These coolers are installed in front of air-cooled condensers to precool outdoor air before entering the condensers. A simulation analysis on an air-cooled chiller equipped with a direct evaporative cooler showed that when head pressure control is used, the cooler enables the condensing temperature to drop by 2.1–6.2°C, resulting in a 1.4-14.4% decrease in chiller power and a 1.3–4.6% increase in the refrigeration effect. When the chiller with the cooler operates under condensing temperature control, where condenser effectiveness is enhanced by staging all condenser fans, there is a savings in chiller power of 1.3-4.3% in some operating conditions in which the drop in compressor power exceeds the additional condenser fan power due to the pressure drop across the cooler.
No takes yet. Share an insight, caveat, or question.
Yu et al. (2005) studied this question.