Answers are grounded in this paper and cite their sources.
A charge simulation method is used to represent sheathed, three-core, belted cables having circular conductors. Each conductor is represented by Nc infinite line charges arranged in a circular pattern inside the conductor. The sheath is represented by Ns infinite line charges arranged in a circular pattern, outside the sheath. It is shown that if the total number of representative charges is in the range of 60 to 80, a very accurate simulation is achieved. For best overall accuracy, the Ns/Nc ratio should be kept in the range of 1.5 to 2.1. Under such conditions, the percentage potential error is normally below 0.2% whereas the field deviation angle is less than 0.3 degrees.
No takes yet. Share an insight, caveat, or question.
Malik et al. (1985) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: