The decarbonization of isolated island power systems is hindered by dependence on diesel generation, limited operational flexibility, and pronounced seasonal demand variability. Lampedusa constitutes a representative Mediterranean case study, characterized by an isolated diesel-based power system with limited renewable energy integration and significant tourism-driven load fluctuations. This study proposes an integrated techno-economic optimization framework for the design and operation of a hybrid island microgrid combining photovoltaic, wind, and wave energy converters with battery energy storage systems (BESSs) and existing diesel generation. The analysis is based on a deterministic hourly resolution dispatch model implemented in MATLAB 2025a and coordinated by an energy management system (EMS), accounting for operational constraints, diesel minimum-load requirements, renewable technology diversification constraints, and battery storage dynamics. The optimal system configuration is determined using a genetic algorithm that minimizes the levelized cost of energy (LCOE) over a discrete design space. Under an annual electricity demand of 33.8 GWh, the optimal configuration achieves a renewable penetration of approximately 65% with a minimum LCOE of 0.1719 €/kWh, requiring 6.0 MW photovoltaic capacity, 3.0 MW wind capacity, 0.5 MW wave energy capacity, and 5.2 MWh BESS energy capacity. Renewable penetration targets exceeding 70% lead to infeasible operating solutions under the imposed system constraints.