This study develops a reduced IEC 60287-based thermal model and an IEC-informed neural-network approximation for ampacity prediction in a 132 kV directly buried aluminium cable reference system. The analytical implementation is calibrated at a single CYMCAP baseline condition for a 132 kV, 1000 mm2 aluminium, XLPE-insulated and HDPE-sheathed cable, for which CYMCAP gives 799.486 A. The numerical design is a deterministic full-factorial Cartesian grid over five variables: soil thermal resistivity, burial depth, ambient soil temperature, allowable conductor temperature, and a bounded screen-loss scenario factor. This design yields 221,760 parameter combinations spanning the prescribed installation and thermal ranges. The model-development run underlying the reported accuracy metrics used 16,000 fitting cases and a 4000-case hold-out interpolation set. Against the reduced IEC 60287 targets, the neural model achieved a mean absolute percentage error of 0.141%, a root-mean-square error of 1.008 A, and R2 = 0.9999. The CYMCAP comparison is explicitly limited to the single calibration point and is not presented as independent multi-point CYMCAP validation. Sensitivity results for soil thermal resistivity and burial depth reproduce the expected monotonic trends, but burial-depth results are interpreted as sensitivities of the calibrated reduced model because the empirical mutual-heating factor is held fixed. The study therefore demonstrates high-fidelity approximation of the stated reduced IEC 60287 function within the sampled domain, rather than universal cable-system verification. The historical subset-selection seed was not retained, so exact reproduction of the neural-network run is not possible.
No takes yet. Share an insight, caveat, or question.
Mutepe et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: