Frost formation on air coolers causes energy losses and operational disruptions in cold stores. This study investigates an ionic liquid-based open absorption system for frost-free air conditioning of cold stores. A dual-circuit absorber–regenerator test bench was developed to experimentally characterize the system under relevant operating conditions. The absorber and regenerator were evaluated using the mass transfer coefficient k m and Sherwood number Sh . Sherwood numbers in the range of Sh ≈ 4.4 − 7.0 were obtained, corresponding to mass transfer coefficients of k m ≈ 9.1 − 14.6 mm/s . The Sherwood number was found to be largely independent of desiccant solution mass flow rate and cooling or heating temperature, indicating gas-side diffusion-limited mass transfer with stable liquid-film wetting. Compared with a conventional air cooler, the absorber-based system prevented frost formation and maintained stable cooling performance while allowing regeneration using low-grade waste heat from the refrigeration system at 42 ° C. Frosting and defrosting losses in an idealized conventional system were found to account for at least 8% of the cooling energy. A system-level energy assessment showed that even the lab-scale absorber-based system could reduce electrical energy demand by 1.4 ± 0.6 % compared with the idealized conventional system. For a full-scale system operating under non-ideal conditions, the achievable savings are expected to be considerably higher. Moreover, the heat exchanger of the absorber-based system can be built 25% smaller while providing the same cooling capacity, as its performance is not degraded by frost formation. These findings demonstrate the potential of absorber-based systems for frost-free, stable, and energy-efficient cold store conditioning.
No takes yet. Share an insight, caveat, or question.
Hochwallner et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: