Answers are grounded in this paper and cite their sources.
Space-charge measurement is increasingly used to evaluate internal field distributions in HVDC cables, making quantitative uncertainty assessment essential for testing applications. Using pulsed electro-acoustic measurements on a full-scale cable with polymer and aluminum acoustic couplers under varied S/N conditions, the uncertainty of the field distribution was assessed. The polymer coupler with numerical Laplace deconvolution achieved uncertainties generally within a few percent, whereas the conventional aluminum element under low S/N conditions produced uncertainty approaching 20%. The uncertainty also depended on the impulse-response waveform used for deconvolution. Waveform S/N ratio, deconvolution method, and choice of impulse response are essential factors to verify that the uncertainty in the field distribution remains within acceptable limits.
No takes yet. Share an insight, caveat, or question.
Fuse et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: