Tropical coastal regions face rapidly growing cooling demand, increasing pressure on electricity systems and freshwater resources. Conventional water-cooled chillers are energy- and water-intensive, exacerbating grid vulnerability and water scarcity under hot, humid conditions. Here we present a comparative techno-economic assessment of three district cooling strategies: a conventional chiller system, a ground heat exchanger-assisted system, and a geologic seawater air-conditioning system that accesses cold seawater through inland wells. Using a case study at the University of Puerto Rico at Río Piedras, we show non-evaporative systems reduce water use and operating costs. The ground heat exchanger-assisted system lowers the levelized cost of cooling by 52%, while the geologic seawater air-conditioning system achieves 70–90% lower costs than the baseline and eliminates water consumption. It also decreases peak electricity demand, demonstrating a pathway to decouple cooling from water and grid constraints in tropical coastal cities. These findings highlight the potential of non-evaporative district cooling to improve resource efficiency and support resilient cooling infrastructure. Non-evaporative district cooling cuts cooling costs by 52% to 90%, eliminates water use, and reduces peak electricity demand, according to a techno-economic assessment of ground heat exchanger and geologic seawater cooling systems.
No takes yet. Share an insight, caveat, or question.
Oh et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: