Grid-forming (GFM) inverters are required to restore from the faults autonomously. However, the existing priority-based current limiting control (CLC) for the GFM inverter may lead to state transition failures during fault ride-through, including repeatedly mode switching between CLC and constant voltage control (CVC) as well as being locked in CLC. However, existing methods rely on the adjustment of CLC parameters, which simultaneously affects other functions of the GFM inverter, such as fault ride-through capability and transient stability. To address this trade-off, this paper first derives the switching conditions of droop controlled GFM inverter in the phasor diagram. Then, the mechanism of state transition for fault ride-through of the droop-based GFM inverter is revealed. Further, a power-angle switching control is proposed to completely eliminate the issue of repeated mode switching without the need to tune the current angle. Based on this, the current angle can be used to avoid CLC lockout while enhancing transient stability and reactive power support capability. The effectiveness of proposed power angle switching control is validated by numerical simulations.