To verify the feasibility of replacing SF6 by CF3I/N2, we compared their power frequency breakdown performance with the influence of gas pressure, mixing ratio, and electric field utilization coefficient. Under different electric fields and mixing ratios, the power frequency breakdown voltage of CF3I/N2 increases linearly along with gas pressure. Besides, with the rise of the electric field utilization coefficient, the linear growth rate of breakdown voltage along with gas pressure gradually rises. The sensitivity of pure CF3I to electric field is particularly high and can be improved by the addition of N2. The mixture 30% CF3I/70% N2 at 0.3 MPa could replace pure SF6 in equipment requiring a low insulation, but the gas pressure or the content of CF3I need to be increased for higher insulation requirements.