Islanding detection is a crucial technique for distributed generation (DG) system. An islanding detection method based on system identification is proposed in this study. Regarding the grid as an RLC load, a recursive least square method is used to estimate the equivalent RLC parameters. Then a logistic regression classifier is applied to determine whether DG is disconnected from the grid or not by the data sets of the estimated parameters of the system. An experiment demonstrates that the algorithm is effective and fast for detecting an islanding event.