When the frequency of an external periodic input or a forced oscillation (FO) is close to that of an inter-area mode of the power system, resonance can occur, and the oscillations may be observed over a vast geographical region. This makes it challenging to locate the FO source. This paper analyzes the interactions of a forced oscillation with local and inter-area modes to show that the amplitude and phase of the dynamic response near the source location can differ substantially from those of non-source generators during a forced oscillation event. This concept forms the basis of a novel source location method, implemented using the Mahalanobis distance (MD) to identify the likely source as a statistical outlier among the amplitude and phase responses observed in phasor measurement units at the forced-oscillation frequency. Results from a validated model of the 1996 Western Interconnection system blackout events and a 240-bus Western Electricity Coordinating Council system model, along with comparisons with existing methods, demonstrate the effectiveness of the proposed approach. In addition, a confidence metric is proposed to assess the credibility of the potential FO source suggested by the method.
No takes yet. Share an insight, caveat, or question.
KC et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: