Cascading failures in hybrid AC/DC power systems can propagate rapidly through DC-side disturbances, AC branch overloads, topology changes, and islanding, making emergency mitigation a constrained sequential decision-making problem under evolving network structures. This paper proposes a topology-aware graph reinforcement learning framework for active cascading failure mitigation. The proposed graph attention network-proximal policy optimization (GAT-PPO) policy combines an edge-aware graph attention encoder, shared action-conditioned scoring heads for branch disconnection and generation redispatch, a state-dependent physics-constrained action mask, and severity-aware scenario sampling. Case studies on an IEEE 39-bus hybrid AC/DC system show that GAT-PPO and a controlled multilayer perceptron-proximal policy optimization (MLP-PPO) baseline achieve similar performance on the seen base topology, while GAT-PPO attains higher load survival rate (LSR) on unseen rewired topologies. Across five random seeds, the mean unseen-topology advantage is +0.0130 ( p ≈ 0.012). Cross-scale validation yields a mean advantage of +0.0183 ( p ≈ 0.002) on the IEEE 118-bus system, accompanied by stronger reductions in branch tripping and cascade depth, while the IEEE 300-bus system further shows a mean advantage of +0.0181 ( p ≈ 0.011). These results show that topology-aware state representations improve the robustness of emergency mitigation policies under unseen connectivity changes.
No takes yet. Share an insight, caveat, or question.
Zhao et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: