Voltage source converter‐based multi‐terminal HVDC (VSC‐MTDC) system has been considered for interconnecting asynchronous power grids for improved system operation efficiency and reliability. In this study, a frequency response control strategy is proposed for the VSC‐MTDC systems that can enable operating reserves sharing among the interconnected asynchronous grids. The proposed control strategy consists of three frequency control components: MTDC primary frequency control, corrective frequency control, and MTDC secondary frequency control. The MTDC primary frequency control could keep the frequency of a disturbed power grid stable and avoid the frequency dropping into an unacceptable level when a sudden power imbalance event occurs. The corrective frequency control strives to guarantee the settled frequency can be within the predefined secure frequency range. The MTDC secondary frequency control provides a novel optimal allocation strategy for considering the participation of MTDC system for restoring system frequency back to the nominal frequency with the lowest cost. The simulation results, based on a modified IEEE New England 39‐bus system modelled in PSCAD/EMTDC, show the effectiveness of the proposed frequency response control strategies.