Transmission towers are conventionally designed for orthogonal wind directions, although skew winds may induce flexural–torsional coupling that is poorly represented in current design practice. This study investigates wind-induced responses of a transmission tower–line system over wind attack angles of 0°–90°. A 5° angular increment is applied within critical ranges, and the torsional contribution to member stress is quantified through stress decomposition. Skew winds generate a pronounced M-shaped, double-peaked distribution of dynamic unbalanced tension at conductor attachment points. Wind directions of 45° and 75° emerge as critical cases for torsional vibration. At 45°, the peak dynamic tension difference reaches 10.83 kN and the relative torsional angle reaches 9.81 × 10 -3 rad, approximately 75 times the value under orthogonal wind. Structural responses also vary sharply over 30°–45° and 75°–90°, demonstrating strong sensitivity to small directional changes. Under the most adverse 45° case, torsion induced by the unbalanced tension contributes 15.6% of the total member stress. These findings highlighted the skew wind–dynamic tension imbalance–torsional response mechanism and demonstrate that neglecting skew-wind-induced torsion may lead to unconservative transmission-tower design.