A new solution method is introduced to the problem of optimally deploying manual and automatic switches in distribution systems, where the product of two continuous variables and the inverse of a continuous variable are reformulated as a linear relation. This leads to a (mixed integer linear problem) MILP power flow formulation too. The objective function includes cost and reliability. The cost term itself includes capital investment, installation, and maintenance costs (MC) as well as customer interruption cost (CIC); while the reliability term is represented by system average interruption duration index (SAIDI). The problem is formulated as a MILP, which guarantees a global optimal solution. The effectiveness of the proposed method is validated through various case studies and sensitivity analyses on the RBTS4, followed by a comprehensive discussion and analysis of results. The proposed MILP formulation prescribes fewer switches while achieving lower SAIDI, compared to that of a previous MINLP formulation.