Planned feeder maintenance in radial distribution networks requires an alternative supply path when no usable mechanical tie line is available or energized AC loop closing is prohibited. This paper proposes a three-stage quasi-steady-state assessment and coordinated dispatch method using a feeder-reconfigurable soft open point (R-SOP) and heterogeneous distributed generation (DG). No active load shedding is scheduled. Stage I uses full-period forecasts to select connection points and assign asymmetrically rated voltage-source converters (VSCs). Stage II progressively transfers the receiving-area demand to the R-SOP while the maintenance branch remains closed. Opening eligibility is assessed from residual branch current, inter-step voltage variation, and power-flow feasibility before and after opening. Stage III assigns the receiving-side VSC the V/f reference role and updates dispatch through rolling optimization and event triggering. In the modified IEEE 33-bus system, the equal-rated fixed SOP has a receiving-side capacity deficit, whereas the 3.0-MVA R-SOP retains a positive continuous margin. In the main case, the maximum steady-state voltage difference across branch opening is below 0.002 p.u., and all monitored operating constraints are satisfied. With DG available, 27 maintenance branches satisfy the complete operating sequence with the R-SOP, compared with 20 with the fixed SOP. These results establish sequential feasibility at the modeled operating points; switching-scale voltage continuity remains to be validated.