This is the authors' abstract. We don't add key points for this paper.
During the manufacturing process of oil-immersed current transformers, metallic particles may become embedded in the insulation wrapping, and the resulting electric field distortion is one of the primary causes of failure. Historically, the shape of metallic particles has often been simplified to a standard sphere, whereas in practice, these particles are predominantly irregular. In this study, ellipsoidal and flaky particles were selected to represent smooth and angular surfaces, respectively. Using COMSOL Multiphysics® (version 6.2) software, a three-dimensional simulation model of an oil-immersed inverted current transformer was developed, and the influence of defect position and size on electric field characteristics was analyzed. The results indicate that both types of defects cause electric field distortion, with longer particles exerting a greater influence on the electric field distribution. Under the voltage of a 220 kV system, elliptical particles (9 mm half shaft) lead to the maximum electric field intensity of main insulation of up to 45.1 × 106 V/m, while the maximum field strength of flaky particles (length 30 mm) is 28.9 × 106 V/m. Additionally, the closer the particles are to the inner side of the main insulation, the more significant their influence on the electric field distribution becomes. The findings provide a foundation for fault analysis and propagation studies related to the main insulation of current transformers.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Lou et al. (2025) studied this question.